Is Electrical Noise Affecting Your Process Signals?

Process Control & Automation | Technical
05/10/2026

Key Takeaways

  • Unstable readings, jumping values and unexpected offsets can be signs of electrical interference.
  • Low-level measurement signals can be particularly vulnerable when transmitted through electrically noisy environments.
  • Signal conditioning can convert and isolate process signals, helping create a more reliable interface between the sensor and the control system.
  • Converting a low-level sensor signal close to the measurement point can reduce the distance that the more vulnerable signal needs to travel.
  • Galvanic isolation can help address ground-loop and potential-difference problems.
  • Signal conditioning is part of the solution, alongside appropriate installation, cable routing, shielding and grounding.

When readings start jumping, drifting or behaving unpredictably, the sensor may not be the problem.

A temperature sensor can be perfectly accurate at the measurement point and still deliver unreliable information to the control system.

That is because measuring the process is only half the job. The signal also has to make its way from the sensor to the PLC, controller, display or monitoring system, often through an industrial environment filled with motors, drives, switching equipment and power cabling.

And somewhere along that journey, things can get noisy.

Electrical noise can show up as an unstable reading, a value that suddenly jumps, an unexpected offset or an intermittent alarm that is difficult to reproduce. PR electronics identifies equipment including frequency drives, motors and contactors as common sources of electromagnetic interference (EMI) in industrial plants.

The challenge is knowing whether the process has genuinely changed or whether the signal reaching your control system no longer represents what is happening at the measurement point.

That is where signal conditioning becomes important.

What does electrical noise look like?

One of the difficulties with electrical interference is that it does not necessarily cause a complete failure.

The instrument may continue operating. The PLC may continue receiving a value. There may be no obvious fault to investigate.

Instead, you may notice:

  • Unstable readings that continually fluctuate when the process itself appears stable.
  • Jumping values that occur periodically or when nearby machinery starts and stops.
  • Unexpected offsets where the measurement appears consistently higher or lower than expected.

You might also see nuisance alarms, unexplained trips or measurements that become unreliable only under particular operating conditions.

Those symptoms can easily lead you toward the sensor first.

But sometimes the question shouldn’t be “What’s wrong with the sensor?”

It should be:

“What’s happening to the signal after it leaves the sensor?”

Why are some process signals more vulnerable?

The smaller the signal, the more significant unwanted electrical interference can become in comparison with the measurement itself.

Thermocouples are a good example.

A thermocouple generates a very small voltage that varies with temperature. PR electronics notes that these signals can be in the order of tens of microvolts per degree, making interference particularly relevant when that low-level signal must travel through a noisy industrial environment.

But the issue isn’t limited to temperature.

Industrial plants can contain many different signal types, sensors and measurement loops, and they don’t necessarily speak the same electrical language as the system receiving the information.

That gives us two separate problems to consider:

  • Is the signal robust enough to reach its destination reliably?

And:

  • Is it in a format the receiving equipment can correctly use?

Signal conditioning helps address both.

What does signal conditioning actually do?

At its simplest, signal conditioning creates an interface between the measurement device and the system that needs the measurement.

Depending on the application, this may involve converting, isolating, repeating or otherwise conditioning the signal before it reaches the PLC, controller or monitoring system.

ECEFast’s signal-conditioning range includes converters, isolators, transmitters and other devices designed for industrial measurement and control applications.

There are several reasons you might need one.

1. Convert a low-level signal into a more robust one

Imagine taking a very small thermocouple signal and running it for a considerable distance through an industrial plant.

Every metre that signal travels is another opportunity for unwanted interference to influence what arrives at the other end.

One approach is to convert the low-level sensor output close to the measurement point.

For example, a temperature transmitter can convert a thermocouple or RTD signal into a standard industrial signal such as 4–20 mA.

That means the vulnerable low-level signal travels only a short distance before being converted into a signal better suited to transmission through the plant. PR electronics specifically recommends converting low-level signals close to the sensor for this reason.

This also makes integration easier where the PLC or control system is designed to receive a standard process signal rather than the sensor’s native output.

Why is 4–20 mA still so widely used?

Because simple doesn’t necessarily mean outdated.

The 4–20 mA current loop remains widely used in process instrumentation because it provides a robust and practical way of transmitting measurement information and is supported by a huge range of industrial control equipment.

For thermocouples specifically, we’ve covered this in more detail in our article Thermocouple Signal Conversion and Why It’s Essential for Accurate Temperature Monitoring.

That article explains the conversion side of the problem.

Electrical noise introduces another reason why the way a signal is transmitted, matters.

2. Isolate the measurement circuit

Signal conversion isn’t always enough.

Sometimes the problem is the electrical relationship between different parts of the system.

If a measurement loop is connected to ground at more than one point, differences in ground potential can allow unwanted current to flow through the signal wiring. That unwanted current may appear as noise or an offset in the measurement.

This is where galvanic isolation comes in.

An isolator transfers the measurement information while electrically separating different parts of the circuit. PR electronics describes galvanic isolation as a means of breaking the unwanted current path between input, output and supply.

In practical terms, you’re not changing what is being measured.

You’re helping prevent another electrical path from interfering with the measurement on its way through the system.

3. Consider the environment the signal conditioner is going into

There is another point that can easily be overlooked.

Putting a signal isolator into an electrically noisy cabinet doesn’t automatically make the problem disappear.

The signal-conditioning equipment itself also operates within that electromagnetic environment.

For applications exposed to significant interference, characteristics such as EMC immunity and the equipment’s suitability for the intended industrial environment need to be considered as part of product selection. PR electronics recommends looking at documented EMC performance rather than treating isolation voltage alone as the complete picture.

This is where product selection becomes application-specific.

The right solution depends on the sensor, signal type, required output, control system, isolation requirements and operating environment.

Signal conditioning isn’t a substitute for good installation

This is important.

Electrical noise problems shouldn’t automatically be treated by installing another device into the signal loop.

Signal and power cable separation, cable routing, twisting, shielding, grounding and cabinet layout can all influence how interference gets into a measurement circuit in the first place. PR electronics’ EMI guidance treats these installation considerations together with signal and equipment selection.

ECEFast’s role becomes particularly relevant once you reach the measurement and signal-conditioning side of the problem.

For example:

  • Does the sensor output need to be converted?
  • Does the input need isolation?
  • Is there a ground-loop issue?
  • Would converting a low-level signal closer to the measurement point improve its reliability?
  • Does the control system require a different signal from the one being produced in the field?

As the exclusive distributor of PR electronics in Australia and New Zealand, ECEFast has direct access to a broad range of signal conditioning, isolation and conversion technologies, backed by local application support.

The objective isn’t to add another device simply because a signal is unstable. It is to understand what is happening within the measurement loop and determine whether conversion, isolation or another signal-conditioning approach is actually required.

Don’t just smooth out the symptom

It can be tempting to solve an unstable reading by adding filtering or damping.

And there are applications where filtering is useful.

But if electrical interference is the underlying problem, smoothing the displayed value may only disguise what is happening.

PR electronics recommends identifying and addressing the source first because increased damping can slow the measurement response while leaving the underlying interference unresolved.

A steadier number on the screen does not necessarily mean you have a better measurement.

The objective is to preserve the integrity of the signal itself.

Getting the right signal to the right place

Reliable process measurement doesn’t stop at the sensor.

The measurement has to leave the sensor, travel through the plant and arrive at the control system in a form that can be interpreted accurately and reliably.

When that isn’t happening, it is worth looking beyond the sensing element.

Unstable readings. Jumping values. Unexpected offsets.

They may be telling you something about the process.

But they may also be telling you something about the signal path.

ECEFast supplies PR electronics signal conditioning solutions, including converters, isolators and transmitters for industrial measurement and control applications.

Experiencing unreliable process signals?

If you’re dealing with unstable measurements, signal compatibility problems or an application requiring signal conversion or isolation, talk to ECEFast about your application.

Frequently Asked Questions

K
L
What causes electrical noise in industrial process signals?

Electrical equipment including variable frequency drives, motors, contactors and switching equipment can generate electromagnetic interference. Depending on the installation, that interference can couple into instrumentation wiring and influence measurement signals.

K
L
What are the signs that electrical noise may be affecting a signal?

Common symptoms can include unstable readings, sudden changes in value, unexpected offsets, nuisance alarms or measurements that appear to change when nearby electrical equipment operates.

K
L
What does a signal conditioner do?

A signal conditioner sits between field instrumentation and the receiving system and can perform functions such as signal conversion and electrical isolation. ECEFast supplies signal-conditioning devices including converters, isolators and transmitters for industrial applications.

K
L
Why convert a thermocouple signal to 4–20 mA?

Thermocouples generate very small voltage signals. Converting the measurement closer to the sensor reduces the distance that this low-level signal needs to travel and provides a more robust industrial signal for transmission to downstream equipment.

K
L
What is galvanic isolation?

Galvanic isolation electrically separates sections of a measurement circuit while allowing the measurement information to pass between them. It can be used to break unwanted current paths associated with differences in ground potential.

K
L
Can signal conditioning fix every electrical noise problem?

No. Signal conditioning can address important issues such as signal conversion and isolation, but good cable routing, shielding, grounding and installation practices also form part of managing EMI.

Brendan Dineen

Justin Marven

Managing director - ECEFast

Justin Marven is the Managing Director of ECEFast and has been helping Australian industry solve measurement and monitoring challenges for more than 30 years. Since joining ECEFast in 1997, Justin has progressed from Sales Manager to General Manager and now Managing Director, giving him a unique perspective on the technologies, industries and customers the business supports. His extensive experience in industrial instrumentation and process measurement enables him to share practical insights that help organisations improve safety, efficiency and operational performance.